Place of Origin:
Switzerland
Brand Name:
Endress+Hauser
Insertion flowmeter with long-term stability as remote version with up to 4 I/Os. Flexible, convenient programming based on 21 standard gases or freely definable gas mixtures. Measurement of utility and process gases as well as gas mixtures in circular piping or rectangular ducts.
| Parameter | Specification |
|---|---|
| Max. Measurement Error | Gas: 1.0% o.r. (10 to 100% o.f.s.), 0.1% o.f.s. (1 to 10% o.f.s.) |
| Measuring Range | 20 to 733,501 kg/h (44 to 1,669,340 lb/h) |
| Medium Temperature Range | -40 °C to +180°C (-40 °F to +356°F) |
| Max. Process Pressure | -0.5 to 20 bar_g (-7.25 to 290 psi_g) |
| Nominal Diameter Range | DN 80 to 1500 (3 to 60") |
| Ambient Temperature Range | -40 to 60°C (-40 to 140°F) Optional: Transmitter: -50 to 60°C (-50 to 140°F), Sensor: -60 to 60°C (-60 to 140°F) |
| Category | Details |
|---|---|
| Measured Variables | Mass flow, temperature, standard volume flow, volume flow, Free air delivery, velocity, heat flow, energy flow, density |
| Transmitter Housing Material | Aluminium, AlSi10Mg, coated; Polycarbonate |
| Degree of Protection | IP66/67, Type 4X enclosure; Sensor: IP68, Type 6P (optional) |
| Display/Operation | 4-line backlit display with touch control; Configuration via local display and operating tools; Remote display available |
| Outputs | 4-20 mA HART (active/passive); 4-20 mA (active/passive); Pulse/frequency/switch output (active/passive); Relay output |
| Inputs | Status input; 4-20 mA input |
| Digital Communication | HART, Modbus RS485 |
| Power Supply | DC 24V; AC 100 to 240V |
Send your inquiry directly to us