Place of Origin:
china
Brand Name:
Honeywell
Wall-mounted distributed optical fiber linear temperature fire detector
Introduction
The distributed optical fiber linear temperature fire detector consists of a sensitive component and a signal processing unit connected to it. The sensitive component of the distributed optical fiber linear temperature fire detector is a temperature-sensitive optical fiber, which transmits the signal to the signal processing unit (distributed optical fiber temperature measurement host) through the temperature-sensitive optical fiber, which can achieve temperature measurement and positioning over a long dist ance.
4 channels, 2.5km per channel/2 channels, 5km per channel, positioning accuracy 0.1m, temperature resolution 0.1℃, temperature measurement accuracy 0.2℃.
Complete alarm function: It has a series of alarm functions such as temperature threshold, temperature change rate and temperature peak, fiber break alarm, etc.
It can be installed on the wall or in the cabinet.
Implementation standards GB16280-2014, Q/XSSEL019-2020, GB3836.1-2010, GB3836.4-2010, GB3836.20-2010.