Product Details
Measurement Principle:
Optical Scattering Principle
Measurement Range:
0 - 20mg/m³
Indication Error:
≤ ± 10%F.S.
Minimum Detection Limit:
0.01mg/m³
Zero - Point Drift:
± 2%F.S./168h
Span Point Drift:
± 2%F.S./168h
Highlight:

Flue Gas Dust Sensor Module

,

KGD YQ 540 Dust Sensor Module

,

Flue Gas Dust Sensor

Payment & Shipping Terms
Minimum Order Quantity
1PCS
Packaging Details
each unit has individual box and all boxes are packed in standard packages or customers requests available
Delivery Time
5-8 work days
Payment Terms
L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability
1000 Piece/Pieces per Week negotiable
Product Description

Flue Gas Dust Sensor Module KGD - YQ - 540

Product Introduction

The KGD - YQ - 540 Flue Gas Dust Sensor Module adopts the optical scattering principle and can accurately detect the mass concentration of suspended particulate matter in the flue gas per unit volume. When the dust particles in the sample gas pass through the laser beam in the constant - temperature measuring gas cell, a light scattering signal is generated. Then, the photoelectric converter converts the scattered light signal into an electrical signal, and the real - time particulate matter mass concentration data is obtained by calculating the relationship between the signal intensity and the concentration. The product complies with the detection requirements of the national standard HJ 76 - 2017 "Technical Requirements and Detection Methods for Continuous Emission Monitoring Systems of Flue Gas (SO₂, NOₓ, Particulate Matter) from Stationary Pollution Sources.

Flue Gas Dust Sensor Module KGD - YQ - 540 0

Product Features

  • High sensitivity, with a minimum detection limit of up to 0.01mg/m³.
  • Modular design, compact structure, and easy to install.
  • Adopts an ultra - low range design, suitable for low - concentration flue gas detection.
  • Constant - temperature heating effectively prevents condensation.

Technical Parameters

Measurement Principle Optical Scattering Principle
Measurement Range 0 - 20mg/m³
Indication Error ≤ ± 10%F.S.
Minimum Detection Limit 0.01mg/m³
Zero - point Drift ± 2%F.S./168h
Span Point Drift ± 2%F.S./168h
Gas Temperature ≤ 300 °C
Data Update Frequency 1s /per time
Working Conditions -20 - 50 °C; 5 - 95%RH (Non - condensing)
Storage Conditions -40 - 85 °C; 5 - 95%RH (Non - condensing)
Anti - clogging Measure Gas - curtain Protection
Working Voltage DC 12V + 0.5V, Ripple < 100mV
Average Working Current < 500mA
Communication Interface UART_TTL (3.3V)
Product Dimensions (WHD) 272mm * 111mm * 193mm