logo
Home > products > Gas Detector Sensor >
Flow Guiding Type Gas Sampling Method Direct Insertion Oxygen Analyzer KGD-MQ-512 50mm Pipe Diameter For Industrial

Flow Guiding Type Gas Sampling Method Direct Insertion Oxygen Analyzer KGD-MQ-512 50mm Pipe Diameter For Industrial

KGD-MQ-512 Industrial Oxygen Analyzer

50mm Pipe Diameter Oxygen Analyzer

Direct Insertion Oxygen Analyzer

Place of Origin:

CHINA

Brand Name:

KACISE

Certification:

CE

Model Number:

KGD-MQ-512

Contact Us
Request A Quote
Product Details
Gas Sampling Method:
Flow - Guiding Type
On - Site Installation Method:
Flange Connection (DN40)
Gas Path Interface:
Standard Interface (6mm)
Pipe Diameter:
50mm
Waterproof:
IP65
Sampling Probe Length:
500/1000/1500mm (customizable)
Highlight:

KGD-MQ-512 Industrial Oxygen Analyzer

,

50mm Pipe Diameter Oxygen Analyzer

,

Direct Insertion Oxygen Analyzer

Payment & Shipping Terms
Minimum Order Quantity
1PCS
Packaging Details
each unit has individual box and all boxes are packed in standard packages or customers requests available
Delivery Time
5-8 work days
Payment Terms
L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability
1000 Piece/Pieces per Week negotiable
Product Description

Direct - Insertion Oxygen AnalyzerKGD-MQ-512

Product Introduction

The KGD - MQ - 512 Direct - Insertion Oxygen Analyzer uses a high - precision zirconia sensor and has an integrated direct - insertion sampling design. It can quickly and accurately conduct on - line detection of the oxygen content in flue gas generated during the combustion process of various common combustion equipment.

Flow Guiding Type Gas Sampling Method Direct Insertion Oxygen Analyzer KGD-MQ-512 50mm Pipe Diameter For Industrial 0

This product is widely applied in industries such as petrochemical, power, chemical, steel, metallurgy, building materials, and textile. Through real - time on - line detection and analysis, it monitors the residual oxygen content in flue gas generated during fuel combustion. By understanding the combustion degree of fuel in combustion equipment, it guides operators to adjust combustion control, reduce waste, and lower energy consumption, ultimately achieving the goals of energy conservation, emission reduction, and environmental protection. The KGD - MQ - 512 Direct - Insertion Oxygen Analyzer features high temperature resistance, high accuracy, long service life, and fast response.

 

Product Features

  • High - precision zirconia sensor with fast response and long service life.
  • Adopts a new - type sampling probe with a flow - guiding gas - sampling design, which can automatically introduce the sample gas.
  • The product can be used continuously for a long time in high - temperature environments within 700℃.
  • Protection grade IP65, suitable for various environments and resistant to harsh weather.
  • The oxygen concentration can be calibrated on - site with air or standard gas to ensure measurement accuracy.
  • Full - process alarm function. When the oxygen content exceeds the alarm set value, a contact alarm signal will be issued.
  • High - temperature protection for important components. When the internal temperature of the meter head is too high, a temperature alarm prompt will be issued.
  • Adopts two signal transmission methods, RS485 and 4 - 20mA, to meet various on - site working conditions.

Technical Parameters

Items Details
Gas Sampling Method Flow - guiding type
On - site Installation Method Flange connection (DN40)
Gas Path Interface Standard interface (6mm)
Pipe Diameter 50mm
Waterproof IP65
Sampling Probe Length 500/1000/1500mm (customizable)
Applicable Flue Gas Temperature 0 - 700℃
Screen LCD screen (128*160)
Measurement Range Range 0 - 25%, resolution 0.1%
Measurement Accuracy ±2%F.S.
Repeatability ≤ ±1%
Stability ±2%F.S./7D
Response Time T90 < 15s
Relay Output 2 groups
Signal Output RS - 485 and (4 - 20)mA
Power Supply DC24V±10%